Earth Notes: 16WW Microgeneration Merit Order
Updated 2025-04-17.grid-tied PV generation capacity ~5kWp(e), ~4.5kWp(e) G83 inverters, AC-coupled, half east-facing, half west-facing, slope ~23° in each case.
Merit order
As of there is a 'merit order' of grid-tied PV generation use, best first:
- Direct consumption in the house.
- Absorption by the Enphase AC-coupled battery up to kW/kWh capacity (~1.3/~6 as of ).
- Power-limited spill to grid (max ~250W).
- Diversion via myenergi Eddi:
- To the DHW cylinder up to kW/kWh capacity (~3/~6). Always takes priority over Thermino so as to minimise heat pump DHW runs when there is only marginal diversion available.
- To the Sunamp Thermino heat battery up to kW/kWh capacity (~3/~7).
- Spill to grid. G83 limit / G59 was waived by DNO, so nominally unlimited but in practice ~4kW maximum.
Also, when grid frequency drops below 49.9Hz (~6% of the time), any automated diversion/boost is suspended: script/myenergi/eddiFreqResponse-netrc.sh
.
Essentially nothing is spilled to grid or diverted during the winter.
Having a lower static export margin in March and September, or a dynamic margin that is lower when (say) the heat storage level is lower, or when a pasteurisation cycle is pending, might cover more of the DHW for those shoulder months in place of grid power. But maybe spilling the extra to grid, and reimporting some (or indeed covering some from the Enphase electrical storage) and using the heat pump with better CoP, is better for the planet overall.
Historic
When the first PV was installed the implied merit order was:
- Direct consumption in the house.
- Spill to grid.
When the first Enphase ACB (AC Battery) module was installed:
- Direct consumption in the house.
- Absorption by the Enphase AC-coupled battery up to kW/kWh capacity (~0.27/~1.1).
- Spill to grid.
...
2025-03-24: snapshot
The merit order as of EOD is:
- Direct consumption in the house.
- Absorption by the Enphase AC-coupled battery up to kW/kWh capacity (~1/~5).
- Power-limited spill to grid (max ~250W).
- Diversion via myenergi Eddi:
- To the DHW cylinder up to kW/kWh capacity (~3/~6). Always takes priority over Thermino to minimise heat pump DHW runs when only marginal diversion.
- To the Sunamp Thermino heat battery up to kW/kWh capacity (~3/~7).
- Spill to grid. G83 limit / G59 was waived by DNO, so nominally unlimited but in practice ~4kW maximum.
Also, when grid frequency drops below 49.9Hz (~6% of the time), any automated diversion/boost is suspended: script/myenergi/eddiFreqResponse-netrc.sh
.